Upgrade Supply Flame Scanner PT. PJB UBJOM Tanjung Awar – Awar
ID PROJECT:
19HO-094ME
CUSTOMER:
PT PJB UBJOM PLTU Tanjung Awar – Awar
PROJECT TITLE:
Upgrade Supply Flame Scanner PT. PJB UBJOM Tanjung Awar – Awar
TYPE:
Part
EQUIPMENT NAME:
ZPF-1200IR ProFlame Scanner by Zeeco
SCOPE OF WORK:
Supply 18 Unit Flame Scanner
WEIGHT KGS:
2
YEAR BUILT:
2020
CODE/STD:
IP66, NEMA 4X
Our Objective
Normalization of Flame Scanner instrument on 2nd Boiler Burner Unit so that it can monitor the burner flames in real-time.
Challenges we faced
Replacing the old & obsolete Flame Scanner with new model
Required specifications are as follows; Nema 4X & IP66 certification, 24VDC or 220VAC power input, Electronics that can withstand temperature range between -40degF (minimum) and 150degF (maximum), Fiber optic that can withstand max temperature of 752degF / 400degC
We did
Welded Mounting Heads on the side of the coal burner, and mounted it there
Installed the outer & inner carrier
Installed the fiber optic used for the flamescanner
Installed the Zeeco(TM) FlameScanner module as a system upgrade
Calibrated the flamescanner onsite using Zeeco(TM)-provided software
Commissioned flame scanner system from local panel
Commissioned flame scanner system from CCR
Ran a Reliability Run (RR) for 5 days straight
Commisioning by Principal
For any project inquiries, feel free to contact us
Additional capabilities have been added to the organization to include technical assistance and support, installation, maintenance of products and design of systems.